INSTALLATION MANUAL
ROOM AIR CONDITIONER
WALL MOUNTED TYPE
NO.0010523234
Read this manual before installation
Explain sufficiently the operating means to the user
according to this manual.
HSU-12HEA03/R2-I
HSU-18HEA03/R2-I
HSU-09HEA03/R2-I
Vue de la page 0
1 2 3 4 5 6 ... 12 13

Résumé du contenu

Page 1 - INSTALLATION MANUAL

INSTALLATION MANUALROOM AIR CONDITIONERWALL MOUNTED TYPENO.0010523234Read this manual before installationExplain sufficiently the operating means to t

Page 2 - No.00105

CETutti i prodotti sono conformi alle seguenti normative europee:- Direttiva 73/23/EEC Basso Voltaggio - Direttiva 2006/95/EC Basso Voltaggio - Dirett

Page 3 - Selection of pipe

Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.ChinaCETodos los productos están en conformidad con las siguientes NormativasEuropeas:- Bajo Volt

Page 4 - Indoor unit

Questo prodotto contiene gas fluorurati ad effetto serra inclusi nel Protocollodi Kyoto. Non liberare tali gas nell’atmosfera.Tipo di refrigerante: R4

Page 5

Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China11+2=kgR410A2kg2=1=BCDFEkgContains fluorinated greenhouse gasescovered by the Kyoto Protocol

Page 6

No.001051.Driver2.Hacksaw3.Hole core drill4.Spanner(17,19 and 26mm)5.Torque wrench(17mm,22mm,26mm)6.Pipe cutter7.Flaring tool8.Knife9.Nipper 12.Reamer

Page 7 - Outdoor unit

Liquid pipe ( )For 09K .12K6.35mm(1/4")Gas pipe ( ) 9.52mm(3/8")For 18K 6.35mm(1/4")12.7mm(1/2")Fixing of outdoor unitIndoor

Page 8

Indoor unit1.Fitting of the Mounting Plate and Positioning of the wall Hole2.Making a Hole on the Wall and Fitting the Piping Hole CoverWhen the mount

Page 9 - 3.On Drainage

Indoor unitFixing the indoor unit body[Other direction piping]Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by pr

Page 10

Indoor unit1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.The type of

Page 11

Outdoor unit1.Installation of Outdoor Unit2.Connection of pipesInstall according toTo bend a pipe, give the roundness as large as possible not to crus

Page 12

Outdoor unit5.Purging Method:To use vacuum pumpDetach the service port's cap of 3-way valve, thevalve rod's cap for 2-way valve and 3-way&ap

Page 13

1.Cut pipe3.Insert the flare nut4.Flare pipeIt becomes high midway.The end is immersedin water.It waves. The gap with the groundis too smallLess than